Vector Control Chassis Type Frequency Converter Connecting-up
SIEMENS AG 476 869 4070 76 J AB-74
SIMOVERT MASTERDRIVES Operating Instructions 7-11
The following connections are provided on the control terminal strip:
♦
10 V aux. voltage (max. 5 mA) for the supply of an external
potentiometer
♦
2 analog inputs, can be used as current or voltage input
♦
2 analog outputs, can be used as current or voltage output
Terminal Designation Significance Range
13 P10 V +10 V supply for ext.
potentiometer
+10 V ±1.3 %,
Imax = 5 mA
14 N10 V -10 V supply for ext.
potentiometer
-10 V ±1.3 %,
Imax = 5 mA
15 AI1+ Analog input 1 + 11 bit + sign
16 M AI1 Ground, analog input 1 Voltage:
17 AI2+ Analog input 2 + ± 10 V / Ri = 60 kΩ
18 M AI2 Ground, analog input 2 Current: Rin = 250 Ω
19 AO1 Analog output 1 10 bit + sign
20 M AO1 Ground, analog output 1 Voltage:
21 AO2 Analog output 2 ± 10 V / Imax = 5 mA
22 M AO2 Ground, analog output 2 Current: 0...20 mA
R ≥ 500 Ω
Connectable cross-section: 1.5 mm² (AWG 16)
Terminal 13 is at the top when installed.
Table 7-6 Control terminal strip X102
The connection for a pulse encoder (HTL unipolar) is provided on the
control terminal strip.
Terminal Designation Significance Range
23 - V
SS
Ground for power supply
24 Track A Connection for track A HTL unipolar
25 Track B Connection for track B HTL unipolar
26 Zero pulse Connection for zero pulse HTL unipolar
27 CTRL Connection for control track HTL unipolar
28 + V
SS
Power supply pulse encoder
15 V
Imax = 190 mA
29 - Temp
Minus (-) connection
KTY84/PTC KTY84: 0...200 °C
30 + Temp
Plus (+) connection
KTY84/PTC
PTC: R
cold
≤ 1.5 kΩ
Connectable cross-section: 1.5 mm² (AWG 16)
Terminal 23 is at the top when installed.
Table 7-7 Control terminal strip X103
X102 – Control
terminal strip
X103 – Pulse
encoder connection